Ultra High Efficiency Fan Coil Units w/ DC Inverter Fan Motors
DC-Inverter fan motors run more efficiently and use less power than regular fan motors. Additionally, they are far quieter than a standard fan unit, you can hardly hear them running. And using a hermetically sealed fan motor means years of trouble free service because dust, salts, acids, and moisture cannot get inside. Did we mention more efficient? DC-Inverter fan motors use up to 75% less electricity to do the same job. Chiltrix Ultra-Slim DC-Inverter CXI FCUs are 110-130V 60Hz.
Chiltrix DC Inverter Fan Coil Units
Chiltrix | Cooling | Heating | Water | Head | Air CFM | dB | dB | Power | Power | Net | Shipping |
Model | BTU | BTU | GPM | Loss (Ft.) | Volume | High | Low | Watts High |
Supply | Dimensions Inches | Dimensions Inches |
CXI120 | 11,877 | 9,733* | 2.5 | 9.3 | 340 | 39 | 28 | 22 | 115v 50/60Hz | 51.2W x 5.1D x 26.4H | 52.8W x 7,1D x 28.7H |
CXI85 | 8,498 | 7,800* | 1.8 | 9.2 | 270 | 37 | 28 | 21 | 115v 50/60Hz | 43.3W x 51.D x 26.4H | 44.9W x 7.1D x 28.7H |
CXI65 | 6,451 | 5,667* | 1.3 | 4.4 | 188 | 32 | 27 | 18 | 115v 50/60Hz | 35.4W x 5.1D x 26.4H | 37.0W x 7.1D x 28.7H |
CXI34 | 3,379 | 3,013* | 1.2 | 3.6 | 94 | 30 | 24 | 14 | 115v 60Hz | 27.6W x 5.1D x 26.4H | 29.1W x 7.1D x 28.7H |
HW72 Export Only |
7,200 | 6,640 | 1.9 | 5.1 | 512 | 46 | 35 | 40 | 220 50/60Hz | 31W x 9D x 11H | 36W x 15D x 11H |
*CXI values listed are at Chiltrix normal temp of EWT 104F and vary based on configuration, please refer to FCU capacity test data or contact us for more details.
Internal water volumes of CXI: CXI-34=1.03L ,CXI-65=1.94L, CXI-85=2.86L, CXI-120=3.79L
See Ductless Fan Coil Specifications Sheet See Ducted Hydronic Air Handler Specifications Sheet
See Pictures of installed CXI fan coil units
The Chiltrix CXI-series FCUs are the thinnest and quietest ductless chiller fan coil units available. They also use far less electricity to operate than any standard fan coil unit. The HW series is a standard high wall design of standard efficiency. The Chiltrix CX-series chiller heat pump units can work with nearly any brand of fan coil unit, ducted or ductless, as well as hydronic in-floor systems.
Central Ducted Hydronic Systems:
Ducted forced air systems are less efficient than ductless fan coil units due to static pressure drop and duct thermal loss. Ducted systems require a centralized thermostat,and cannot take advantage of individual zones in each room like a ductless system. In new construction, or when adding air conditioning to a building that has no current duct system, the installed cost of a ductless system will be about the same, or less than, installing with a duct system. However, if a central ducted system is your best choice, the Chiltrix system combined with a FirstCo DC-Inverter powered VMB will be your most efficient choice. See Ducted Chiller Fan Coil Sizing Guide And see mini-duct air handler unit info here.
About DC Inverter Fan Motor Technology
Whether it is used for a compressor, a pump, or a fan motor, DC Inverter motors are well known for being more efficient. They also run cooler, last longer, and produce a much lower sound level.
DC Inverter motors have no actual inverter in them, AC power runs through a rectifier circuit converting it to DC power. The DC power is then pulsed in varying frequencies to rotate the motor. The higher the pulse frequency, the faster the motor turns. DC inverter motors are not only up to 20-40% more efficient at a given speed, they also provide the ability to efficiently match the motor speed to the real-time demand saving even more energy. |
Below is the latent heat rejection table for CXI ductless fan coil units based on standard AHRI test condition W44F, 80FdB / 67FwB.
Model | Moisture Removal (L/h) | Sensible Heat Ratio |
CXI-34 | 0.38 | 74% |
CXI-65 | 0.68 | 75% |
CXI-85 | 0.85 | 77% |
CXI-120 | 1.32 | 74% |
Above at max speed.
CXI Fan Speed CFM | CXI-34 | CXI-65 | CXI-85 | CXI-120 |
Air volume(H) | 94.2 | 188.3 | 270.7 | 341.4 |
Air volume(M) | 64.7 | 129.5 | 194.2 | 241.3 |
Air volume(L) | 53.0 | 107.1 | 158.9 | 200.1 |
Reviews
There are no reviews yet.